SI-16
The SI-16 is an alarm zone input sub-controller, that can monitor up to 16 supervised inputs, and control 2 onboard relays.

 
     
 

SI-16
Introduction

The Integrated System 2000 family of hardware was designed to meet the growing requirement for “Open Architecture” electronics in the access control and security marketplace. The SI-16 is an alarm zone input processor that provides the flexibility to meet a wide range of system architecture applications. The alarm input processor family has been in the marketplace for 4 years, and over 25,000
units have been placed in service.
Hardware
· 16 Input Zone
· Plus, Enclosure Tamper and Power
Monitor Inputs
· 2 Output Relays (General Purpose)
· Analog/Digital Conversion Technology
· Supervision of Alarm Zones (User
Selectable EOL)
· Flash Memory for Firmware
· Share Enclosures with Other Processors
  Technology
The SI-16 uses a 32-bit processor, 32- bit Windows DLL(s) and FLASH memory for firmware.
Firmware features coupled with the latest processor technology make this field processor a leader in the industry. Many Dealers/Integrators praise the product for its reliability, ease of installation and competitive price.
Communications
· 2 or 4 Wire RS-485, 19.2 to 38.4 Kbps, Multi-Drop, 4,000 Feet Maximum
· Fiber Optics
· Dedicated Telephone Lines
  Enclosures
The IS2000 field processors are offered either with an enclosure, or without an enclosure. Refer
to the IS2-ENC-1 cut-sheet for details.
Capacity
· 32 SI-16s per SCP (512 Inputs)
· 16,384 Inputs per System
 

Warranty
The Imron Corporation factory warranty period for the IS2000 System is 18 months from the shipment date.

Access Control
· Security Alarm Inputs
· Access Control Inputs
· HVAC and Energy Control Inputs
· CCTV Camera Call-up Input
· Process Control Inputs
 

ELECTRICAL SPECIFICATIONS

· Primary power (DC or AC)
DC input: 12 VDC +/- 15%, 250mA
AC input: 12 VAC +/- 15%, 350mA RMS
· Relay Contacts: 2 Form C, 5A 30VDC or 125 VAC, Resistive
· Inputs (standard): 16 supervised, EOL ,1k ohm 1% 3 watt standard
· Wiring Requirements:
Power: 1 twisted pair, 18 AWG
RS-485: 24 AWG, 4,000ft (1,200m) max., twisted pair(s) with shield
Alarm input: 1 twisted pair, 30 ohms max.
Output: As required for the load

 

GENERAL SPECIFICATIONS

· Physical:
Dimensions: 6 in. W x 8 in. L x 1 in. H (152 mm W x 203 mm L x 25 mm H)
Weight: 10 oz. (290gm) nominal
· Environmental:
Temperature: Operating: 0o C to 70 o C
Storage: -55 o to +85 o C
Humidity: 0% to 95% RHNC


Copyright © Imron Corporation all rights reserved.